Introduction

Manual entry forms are used for data entry by Factry Historian users. There currently are 2 types of forms.

Event form

This manual entry form allows you to manually enter event property values.
The configuration of the form will determine which event types are shown to the user. For each event type, you can configure which properties of those events are shown and which can be manually edited.

Asset properties form

This manual entry form allows you to to manually enter time series data on asset properties .
The configuration of the form determines which asset properties are available to the user and how they are grouped.

Configuring a manual entry form

Create a new manual entry form by going to the manual entry overview in the left menu bar and pressing the Create manual entry form button in the top right corner.

Basic configuration

Enter the basic information

  1. Enter a name
  2. Optionally enter a description
  3. Select a type

Enter the general configuration options

  1. Default time range: the time range the manual entry form will show events for by default (default 24h)
  2. Maximum time range:the maximum time range the manual entry form will allow you to view (default 7d)
  3. Auto refresh interval: how often the manual entry form will automatically refresh (default 30s)
  4. Maximum edit age: the maximum age of an event, determined by its start time, that can be edited (default 24h)
  5. Maximum elevated edit age: the maximum age of an event, determined by its start time, that can be edited by users with elevated privileges (default 24h)
  6. Datetime format: the format in which the start/stop time of the events in the manual entry form will be shown

Manual entry basic configuration

Depending on the selected type the configuration options will appear:

Don’t forget to configure the access rights !

Event form

Event configurations

The event configurations determine which events will be shown in the manual entry form.
To add an event configuration, press the Add event configuration button. This will open the following form.

Manual entry event configuration

  1. Select an asset from the preconfigured asset tree
  2. Select an event type from the configured event types
  3. Optionally enter an asset display name to override the asset name
  4. Optionally enter a column width
  5. Select whether the event is editable or not, editable events can be created, edited and deleted
  6. Select a display color. This is useful for clearly separating different event types in the manual entry forms.
  7. Click Confirm.

Manual entry event configurations

Properties

The configured event type properties determine which properties will be shown and which ones will be editable in the manual entry form.
To add a property, press the Add property button, this will open a form.

Manual entry property

  1. Select an event type property
  2. Enter a display name for the property
  3. Optionally enter a tooltip. This will be shown to the end user when hovering over the event property.
  4. Enter a group. Properties in the same group will be grouped together
  5. Optionally set the order of the property. This determines the order of the properties within the same group. Properties are sorted incrementally.
  6. Select whether the property is editable
  7. Select whether the property is editable on open events (events that have yet finished)

Manual entry properties

Asset properties form

Asset properties

The asset properties determine which assets and asset properties will be available for manual entry.

Manual entry asset properties

There are 2 ways to group the asset properties in the form, by using the existing structure of the asset tree or by assigning a group to each asset property.

Press Configure asset properties.

Manual entry select asset properties

Select the asset properties you want to add to the manual entry form and press Next

Using tree display

  1. Select whether to prefill the asset property name as the display name
  2. Select whether to use the engineering specifications
  3. Enter the default number of decimals to display for numeric properties
  4. Enter whether the property is editable

Click Apply for all if the default configuration can be used for all the asset properties, press next to edit them individually.

Manual entry default asset property configuration with tree display

  1. Enter a display name
  2. Optionally enter a tooltip
  3. Select whether to use engineering specs configured on the measurement linked to the asset property
  4. Optionally set the order of the property. This determines the order of the properties within the same group. Properties are sorted incrementally.
  5. Enter the number of decimals to display for numeric properties
  6. Enter whether the property is editable

Manual entry asset property configuration with tree display

Do this for all the selected asset properties and click Finish.

Manual entry configured asset properties

Using grouping

  1. Select whether to prefill the asset property name as the display name
  2. Select whether to use the engineering specifications
  3. Enter the default number of decimals to display for numeric properties
  4. Enter the default group to add the asset properties to
  5. Enter whether the property is editable

Click Apply for all if the default configuration can be used for all the asset properties, press Next to edit them individually. A default group is necessary to use Apply for all.

Manual entry default asset property configuration

  1. Enter the group to add the asset property to
  2. Enter a display name
  3. Optionally enter a tooltip
  4. Select whether to use engineering specs configured on the measurement linked to the asset property
  5. Optionally set the order of the property. This determines the order of the properties within the same group. Properties are sorted incrementally.
  6. Enter the number of decimals to display for numeric properties
  7. Enter whether the property is editable

Manual entry asset property configuration

Do this for all the selected asset properties and click Finish.

Manual entry configured asset properties with group

Access rights

Only groups that are configured to have access rights will be able to view the manual entry form.
Select the user groups that need access rights by typing their name in the input field.
Select the user groups that have elevated access rights. If a user group has elevated access rights you don not need to add them to the groups with access rights.

Manual entry user groups

Click Save.